Units shall be model, Ceiling/Console/Hideaway type fan coil units as indicated in this section of the website.
COOLING CAPACITY - of the units shall be _____ kWatts Total and _____ kWatts Sensible or greater at conditions of °CWB _____ °CWB entering air temperatures and with a chilled water flow temperature of _____ °C at a flow rate of _____ l/s. Number of rows of coil 3.
HEATING CAPACITY - of the units shall be _____ kWatts or greater at a condition of _____ °C entering air, temperature and with a hot water flow temperature of _____ °C at a warm flow rate of _____ l/s. Number of rows of coil: 1 Row Coil, Standard Hot Water Heating integral with Cooling coil, 4 Pipe Convections, 2 Row Coil Standard Hot Water Heating, 3 Row Coil Low temperature Hot Water Heating.
BASIC UNIT - shall be complete with water coil, one or more centrifugal Fans, and of heavy galvanized steel construction. Units for cooling should be used with a condensate tray. Horizontal unit height shall not exceed 240mm. The fan and motor shall be easily removable for servicing. The coils to be constructed of aluminum fins mechanically bonded to 12.7mm dia tube with plain copper connections. Coils to be leak tested to 1,000 kpa air pressure.
MOTORS - shall be 3 speed permanent split capacitor type with ball bearings.
FANS - shall be centrifugal, forward curved type manufactured from engineering plastics.
ELECTRICAL WIRING - shall meet SECV approval. Test specifications AAS 3103, wired to terminal Junction Box for control components.
EXPOSED CABINETS - shall be interchangeable panels powder coated. The cabinet front panel shall be removable to allow easy installation and service to all major components. Console units shall be fitted with a plinth and ceiling units with back panels. Access to valves and speed controls are to be through hinged access doors adjacent to the adjustable supply air grilles.
FILTERS - all exposed cabinet units to be fitted with Saran net filter medium, fitted in aluminum frames. |